Supply Voltages
Communications
- Dedicated EIA-485 I/O-Net port for communications to host MACH-ProCom or MACH-ProSys controllers
- Baud rate fixed at 76.8 kbps
Universal Inputs
- 24 universal inputs
- 12-bit ADC
- Analog: 0-5 VDC, 0-10 VDC, 4-20 mA, thermistor
- Digital: dry contact
- Impedance:
1 M Ω on 0-5 VDC range,
1 M Ω on 0-10 VDC range,
250 Ω on 4-20 mA range
20 kΩ pull-up for thermistor/dry contact range
- 150 Hz pulse counting (supports flow meters)
- 24 VAC over-voltage protection
|
|
Dimensions
- 17.9 cm L x 13.7 cm W x 3.9 cm H
(7.05" L x 5.39" W x 1.54" H)
Mounting
- #8 clearance holes on 15.6 cm L x 11.0 cm W (6.14" L x 4.33" W)
- Screw depth 25 mm (1")
Weight
Ambient Limits
- Operating: -20 ºC to 55ºC
(-4 ºF to 131 ºF)
- Shipping: -40 ºC to 60 ºC
(-40 ºF to 140 ºF)
- Humidity: 10% to 90%
RH non-condensing
|
|