Processor
  • 50 mHz, high performance, 16-bit embedded microcontroller

Memory
  • 512k NV RAM user database
  • 512k Flash EEPROM operating system firmware and controller configurations

Supply Voltages
  • 24 VAC/VDC, 24 VA max.

Communications
  • EIA-485 @ 76.8 kbps max.
  • EIA-232 @ 57.6 kbps max. PC or Modem
  • SMART-Net™ (16 SMART-Sensors™ max.)

Universal Inputs
  • 8 universal inputs (expandable to 32)
  • 10 bit A/D convertor
  • Analog: 0-5 VDC, 4-20 mA, thermistor
  • Digital: dry contact
  • Impedence:
    15k Ω on 0-5 VDC range 250 Ω on 4-20 mA range 10k Ω on thermistor range
  • 40 Hz pulse counting (supports flow meters)
  • 24 VAC over-voltage protection

Universal Outputs
  • 8 universal outputs (expandable to 32)
  • 8-bit D/A converter
  • Analog: 0-12 VDC
  • Digital: 0-12 VDC
  • Manual ON provides 14.1 VDC
  • LED indicator (glows proportionally)
  • Output power: 75 mA @ 12 VDC
  • 24 VAC over-voltage and short protection

Real-Time Clock
  • ±1 second per day

    Memory/RTC Backup
    • 72-hour capacitor backup
    • Optional battery backup for 1 year lithium (offline)

    Dimensions
    • 21.7 cm L x 13.2 cm W x 4.3 cm H
      (8 1/2" L x 5 3/16" W x 1 11/16" H)

    Mounting
    • #8 clearance holes on 20.3 cm L x 12 cm W
      (8" L x 4 11/16" W)

    Weight
    • 0.4 kg (1.0 lb.)

    Ambient Limits
    • Operating: -20 ºC to 55 ºC (-4 ºF to 131 ºF)
    • Shipping: -20 ºC to 60 ºC (-4 ºF to 140 ºF)
    • Humidity: 10% to 90% RH non-condensing