Protocol
- BACnet®
- MS/TP (EIA-485)
- Reliable Controls® Protocol
- Network (EIA-485/Token Bus)
4 Control-BASIC Programs
- User programmable control strategy
in a readable, BASIC-like language
- 2000 bytes per program
6 Inputs
- 3 Inputs with universal ranges
- Jumper selectable 0–5 VDC, 4–20 mA, thermistor/dry contact
- Input #4 dedicated to the flow sensor
- Input #5 dedicated to the damper position feedback
- Input #6 dedicated to indicate damper at end of position
5 Outputs
- 3 outputs with universal ranges
(base model)
- Scalable 0-12 VDC, 75 mA max.
- Output #4 dedicated to
damper motor (available as floating point on models without actuator)
- Output #5 dedicated to
control direction of rotation
to close
- Single stage TRIAC (T model only)
- Dual stage TRIAC (T model only) - configurable for floating point or 2 stage
|
|
48 Variables
- Selectable standard and custom ranges,
as well as fixed or program-driven
values
- Variable #1 dedicated to flow
calibration
4 PID Loops
- Standard P, PI, or PID controllers
for closed loop control
2 Trend Logs
- Each Trend Log stores 72 samples of
6 points at programmable time intervals
4 Runtime Logs
- Totals the On time and records
the On/Off times of a digital point
- Holds 48 samples
2 System Groups
- Related points can be
grouped in one display
- 50 points/group
1 Weekly Schedules
- 4 On/Off times for each weekday and
2 override days
|
|
5 Custom Tables
- For creating custom input ranges
and Control-BASIC lookup tables
SMART-Net Port
- Networks up to 4 SMART-Sensors
- SMART-Sensor #5 is dedicated to SETUP-Tool
32 Network In Points
32 Network Out Points