Processor
- 25 mHz, high performance
16-bit embedded microcontroller
Memory
- 32k RAM
- 128k Flash EEPROM operating
system firmware and controller configurations
Supply Voltages
- 24 VAC/VDC ±10%
- 25 VA maximum
Communications
- EIA-485 @ 76.8 kbps
- SMART-Net (4 SMART-Sensors max)
SETUP-Tool
- SETUP-Tool used for configuration
|
|
Universal Inputs
- 3 universal inputs
- 10 bit A/D convertor
- Analog: 0-5 VDC, 4-20 mA,
thermistor
- Digital: dry contact
- Impedence:
15k O on 0-5 VDC range
250 O on 4-20 mA range
10k O on thermistor range
- 40 Hz pulse counting
(supports flow meters)
- 24 VAC over voltage protection
Universal Outputs
- 8 bit D/A converter
- Analog: 0-12 VDC
- Digital: 0 or 12 VDC
- Output power: 75 mA @ 12 VDC
- 24 VAC over voltage and
short protection
Triac Outputs
- 24 VAC @ 0.5 A
- Common return
|
|
Velocity Sensors
- Flow-through thermistor
- 0-1" W.C.
Actuator
- Torque: 35 in-lb.
- Brushless DC
Enclosure
Dimensions
- 22.9 cm L x 13.4 cm W x 6.3 cm H
(9” L x 4.8” W x 2.5” H)
Weight
Ambient Limits
- Operating: 0 °C to 40 °C
(32 °F to 104 °F)
- Shipping: -20 °C to 60 °C
(-40 °F to 140 °F)
- Humidity: 10% to 90%
RH non-condensing
|
|