Protocol
- BACnet® - B/IP x 2, Ethernet, MS/TP, and PTP
- HTTP - Hyper Text Transfer Protocol
- Reliable Controls Protocol - Backward compatibility
with previous generation systems
- Modbus - Supports both RTU and TCP in both master and slave configurations
- SMTP - Provides standard email communications for broadcasting email alarms
- SMS - GSM / GPRS modem
- SNMP - Simple Network Management Protocol
12 Inputs
- Universal ranges
- Expandable using MACH-ProPoint expansion modules
- Maximum possible inputs of 128
8 Outputs
- Outputs 1-4 are wired to unpopulated sockets
- Outputs 5-8 are universal (no sockets)
- Expandable outputs using MACH-ProPoint expansion modules
- Maximum possible outputs of 64
|
|
256 Variables
- Selectable standard and custom ranges,
as well as fixed program-driven
values
64 PID Loops
- Standard P, PI, or PID controllers
for closed loop control
- BACnet® loops supported
32 Weekly Schedules
- 4 On / Off times for each weekday and 2 override days
- BACnet® schedules supported
8 Annual Schedules
- Days of the year designated as holidays
- BACnet® calendar supported
20 Custom Tables
- For creating custom scaling functions
64 System Groups
- Allows related points to be grouped on to one display
- 160 points / group
128 Control-BASIC Programs
- User programmable control strategy
in a readable, BASIC-like language
- 3200 bytes per program
|
|
96 Trend Logs
- Each Trend Log stores 512 samples and up to 6 points
- Values recorded at user defined intervals
- BACnet® Trend Logs supported
128 Runtime Logs
- Totals the On time and records the On / Off times of a digital point
- Holds 200 events
128 User Passwords
- Protects access to system
- Each user is assigned a user name
and an access level
16 Custom Units
- 8 analog engineering units
- 8 digital engineering units
SMART-Net Port
- Networks up to 16 SMART-Sensors
Real-Time Clock