Return to the Reliable Controls Homepage Reliable Controls - people & technology you can rely on... Go to the Chinese website | Contact Us | Help |        
Corporate
Products
Email Reliable Controls Email Print Largest Font Size Regular Font Size Small Font Size
BACnet Testing Labs (BTL) Logo
[Listed Device]


AHR Innovation Award 2008 Honorable Mention
MACH-Stat BACnet Space Controller MACH-Stat Header
The Reliable Controls® MACH-Stat™ is a unique, fully programmable BACnet Advanced Application Controller (B-AAC) ideal for mid-sized rooftop equipment, multizone equipment, or small mechanical room applications requiring a completely customizable local display.
This text is replaced by the Flash content.
This text is replaced by the Flash content.
[Features]     [Tech Specs]     [Application Diagram]     [Vision Groups]     [Modules]     [PDF Sheet]
Processor
  • 25 mHz, high performance, 16-bit embedded microcontroller

Memory
  • 64k RAM, for logs and scratch
  • 512k Flash EEPROM for firmware configurations and database
  • Minimum 10-year retention

Real Time Clock (optional)
  • ±1 second per day

Supply Voltages
  • 24 VAC/VDC, 25 VA max.

Communications
  • EIA-485 @ 76.8 kbps max.
  • SMART-Net™ (4 SMART-Sensors max.)

Display
  • 128 x 64 dot matrix LCD with white backlight
  • View area 62 mm x 44 mm
  • Contrast adjust, backlight select

Keypad
  • 5-button conductive rubber

Temperature Sensor
  • Thermistor comes pre-mounted on Input 5 (can also be remote mounted)
  • Range: 0ºC to 40ºC (32ºF to 104ºF)
  • ±0.1ºC (0.18ºF) resolution
  • User calibrated to ±0.1ºC (0.18ºF) accuracy
Configuration
  • SETUP-Tool™ or X-Port™ required for MSet configuration

Mounting
  • Unit mounts directly to single or dual device box

Inputs (8 max.)
  • 4 Universal Inputs
    • 10-bit A/D converter
    • Analog: 0-5 VDC, 4-20 mA, thermistor
    • Digital: dry contact
    • Impedance:
      15k Ω on 0-5 VDC range,
      250 Ω on 4-20 mA range,
      10k Ω on thermistor range
    • 100 Hz pulse counting (supports flow meters)
    • 24 VAC over-voltage protection
  • 2 thermistor/dry contact inputs
  • Humidity input
    • 0.1% resolution
    • 10-90% range
    • ± 1.8% RH accuracy
  • Occupancy input
    • Passive Infrared Radiation (PIR) sensor
    • 64 detection zones
    • 100º horizontal / 82º vertical
    • 5 m (16.4 ft.) max. detection distance
Output Sockets (8 max.)
  • Ships with 8 unpopulated output sockets
  • Output Modules (OMs) sold separately
  • Sockets 1-6 include an 8-bit D/A convertor and can be configured as analog outputs
  • Sockets 1-4 accept any mix of OMs (relay, TRIAC, or universal)
  • Sockets 5-6 must be populated with either 2 universal OMs, or any mix of TRIAC or relay OMs
  • Sockets 7-8 are TRIAC
  • Universal OMs provide 0-12 VDC (analog or digital), 75 mA max. with 24 VAC over-voltage and short circuit protection
  • Relay OMs provide a dry contact for switching DC or AC loads up to 24 V, 0-500 mA
  • TRIAC OMs switch 24 VAC only with current load between 20-500 mA

Dimensions
  • 12 cm L x 14 cm W x 4.3 cm H
    (4 3/4" L x 5 1/2" W x 1 5/8" H)

Weight
  • 0.28 kg (0.615 lb.)

Ambient Limits
  • Operating: -20 ºC to 55 ºC
    (-4 ºF to 131 ºF)
  • Shipping: -40 ºC to 60 ºC
    (-40 ºF to 140 ºF)
  • Humidity: 10% to 90%
    RH non-condensing

Privacy Policy | Terms of Use | License Agreement | Site Map | Send Feedback
Reliable Controls® and the Reliable Controls® logo are registered trademarks of Reliable Controls Corporation. Copyright ©2011. All right reserved.