Protocol
- BACnet®
- MS/TP (EIA-485)
- Reliable Controls®
- Network (EIA-485/Token Bus)
4 Control-BASIC Programs
- User programmable control strategy in a readable, BASIC-like language
- 2000 bytes per program
9 Inputs (max.)
- Inputs 1–4 Universal ranges Jumper selectable: 0–5 VDC,
4–20 mA, thermistor, and dry contact
- Input 5 comes with 10k thermistor - linked
to Override Button
- Input 6 optional 20k setpoint slider or 10k/dry contact
- Input 7 optional Humidity sensor
- Input 8 optional Occupancy sensor
- Input 9 optional CO2 sensor
8 Output Sockets
- Outputs 1–6 accommodate universal or relay modules
- Outputs 7 & 8 accommodate relay modules only
- Universal ranges scalable 0–12 VDC
- Single stage relay - jumper selectable NO/NC
|
|
48 Variables
- Selectable standard and custom ranges, as well as fixed
or program-driven values
4 PID Loops
- Standard P, PI, or PID controllers for closed loop control
3 Trend Logs
- Each trend log stores 150 samples of 6 points at programmable time intervals
8 Runtime Logs
- Totals the on time and records the on/off times of a digital point
- Holds 100 samples
2 System Groups
- Allows related points to be
grouped on one display
- 50 points per group
1 Weekly Schedule
- 4 on/off times for each weekday and 2 override days
|
|
1 Annual Schedules
- Days of the year designated as holidays
5 Custom Tables
- For creating custom input ranges and Control-BASIC lookup tables
16 Custom Units
- 8 analog engineering units
- 8 digital engineering units
SMART-Net Port
- Networks up to 4 SMART-Sensors
32 Network In Points
32 Network Out Points
Warranty
- Industry Recognized 5 Year
- 2 years on CO2 sensor
- 1 year on humidity sensor
Certification
|
|