Return to the Reliable Controls Homepage Reliable Controls - people & technology you can rely on... Go to the Chinese website | Contact Us | Largest Font Size Regular Font Size Small Font Size | Help |        
Corporate
Products

BACnet Testing Labs (BTL) Logo
[Listed Device]


AHR Innovation Award 2008 Honorable Mention
MACH-Stat-ND BACnet Space Controller MACH-Stat-ND Header
The Reliable Controls® MACH-Stat-ND™ is a unique, fully programmable BACnet Advanced Application Controller (B-AAC) ideal for applications that require any combination of space temperature, humidity, Carbon Dioxide, occupancy sensing, local override, and setpoint adjust, in one convenient package.
[Features]     [Tech Specs]     [Application Diagram]     [Modules]     [PDF Sheet]
Protocol
  • BACnet®
    - MS/TP (EIA-485)
  • Reliable Controls Protocol
    - Network (EIA-485/Token Bus)

4 Control-BASIC™ Programs
  • User programmable control strategy in a readable, BASIC-like language
  • 2000 bytes per program

9 Inputs (max.)
  • Inputs 1–4 universal ranges are jumper selectable: 0–5 VDC, 4–20 mA, thermistor, and dry contact
  • Input 5 is 10k thermistor - linked to override button
  • Input 6 optional 20k setpoint slider or 10k/dry contact
  • Input 7 optional humidity sensor
  • Input 8 optional occupancy sensor
  • Input 9 optional CO2 sensor

8 Outputs
  • Sockets 1–6 accept any mix of OMs (relay, TRIAC, or universal)
  • Outputs 7–8 are TRIAC and require no OMs
  • Universal ranges are scalable between 0–12 VDC
  • Relay Modules are jumper selectable NO/NC
48 Variables
  • Selectable standard and custom ranges, as well as fixed or program-driven values

4 PID Loops
  • Standard P, PI, or PID controllers for closed loop control

3 Trend Logs
  • Each Trend Log stores 150 samples of 6 points at programmable time intervals

8 Runtime Logs
  • Totals the On time and records the On/Off times of a digital point
  • Holds 100 samples

2 System Groups
  • Allows related points to be grouped on one display
  • 50 points per group

1 Weekly Schedule
  • 4 On/Off times for each weekday and 2 override days

1 Annual Schedule
  • Days of the year designated as holidays

5 Custom Tables
  • For creating custom input ranges and Control-BASIC™ lookup tables

16 Custom Units
  • 8 analog engineering units
  • 8 digital engineering units

SMART-Net™ Port
  • Networks up to 4 SMART-Sensors™

48 Network In Points

32 Network Out Points

Warranty
  • 5 years
  • 1 year on humidity sensor
  • 2 years on CO2 sensor

Certification


Reliable Controls Facebook Page Reliable Controls Twitter Account Reliable Controls YouTube Account Reliable Controls LinkedIn account
Privacy Policy | Terms of Use | Site Map | Send Feedback
Reliable Controls® and the Reliable Controls® logo are registered trademarks of