Return to the Reliable Controls Homepage Reliable Controls - people & technology you can rely on... Go to the Chinese website | Contact Us | Help |        
Corporate
Products
Email Reliable Controls Email Print Largest Font Size Regular Font Size Small Font Size
BACnet Testing Labs (BTL) Logo
[Listed Device]
MACH-Stat-ND BACnet Space Controller MACH-Stat-ND Header
The Reliable Controls® MACH-Stat-ND™ is a fully programmable, versatile BACnet® controller designed for space control applications where an LCD display is not required.

The MACH-Stat-ND™ can be ordered with optional setpoint slider, humidity sensor, CO2 sensor, and occupancy sensor.
[Features]     [Tech Specs]     [Application Diagram]     [Modules]     [PDF Sheet]
Processor
  • 50 mHz, high performance 16-bit embedded microcontroller

Memory
  • 64k RAM, for logs and scratch
  • 512k Flash EEPROM for firmware configurations and database
  • Minimum 10-year retention

Supply Voltages
  • 24 VAC/VDC ±15%
  • 25 VA maximum

Communications
  • EIA-485 @ 76.8 kbps max.
  • SMART-Net™ (4 SMART-Sensors™ max.)

Temperature Sensor
  • Thermistor comes pre-mounted on Input 5 (can also be remote mounted)
  • Range: 0ºC to 40ºC (32ºF to 104ºF)
  • ±0.1ºC (0.18ºF) resolution
  • User calibrated to ±0.1ºC (0.18ºF) accuracy

Configuration
  • SETUP-Tool™ or X-Port™ required for MSet configuration

Mounting
  • Unit mounts directly to single or dual device box
Inputs (9 max.)
  • 4 Universal Inputs:
    • 10-bit A/D converter
    • Analog: 0–5 VDC, 4–20 mA, thermistor
    • Digital: dry contact
    • Impedance:
      15k Ω on 0-5 VDC range,
      250 Ω on 4-20 mA range,
      10k Ω on thermistor range
    • 100 Hz pulse counting (supports flow meters)
    • 24 VAC over voltage protection
  • 2 Thermistor/Dry Contact Inputs
  • Humidity Input:
    • 10-90% range 0.1% resolution
    • ± 1.8% RH accuracy
    • replaceable sensing element
  • Occupancy Input:
    • Passive infrared radiation (PIR)
    • 5 m/16.4 ft. max detection distance
    • 100º horizontal / 82º vertical
    • 64 detection zones
  • CO2 Input:
    • 0-2000 ppm
    • ± 30 ppm accuracy
    • Auto calibrating
    • Repeatability = ± 20 ppm ± 1 of measured value
    • Linearity = ± 30 ppm
    • Max. drift ± 5% measured value
    • Auto drift correction, 30 ppm/week
    • Maintenance free
  • Override Button linked to
    Input 5
Output Sockets (8 max.)
  • Controller ships with 8 unpopulated, output sockets which require modules that are sold separately
  • 6 Universal Output Sockets:
    • 8-bit D/A converter
    • Analog: 0-12 VDC
    • Digital: 0 or 12 VDC
    • Output power: 75mA @ 12 VDC
    • 24 VAC over voltage and short protection
  • 2 Relay Output Sockets:
    • 24 VAC/VDC @ 0.5 A
    • Common return

Dimensions
  • 12 cm L x 14 cm W x 4.2 cm H
    (4.72" L x 5.5" W x 1.65" H)

Weight
  • 0.28 kg (0.615 lb.)

Ambient Limits
  • Operating: 0 ºC to 40 ºC
    (32 ºF to 104 ºF)
  • Shipping: -40 ºC to 60 ºC
    (-40 ºF to 140 ºF)
  • Humidity: 10% to 90%
    RH non-condensing

Privacy Policy | Terms of Use | License Agreement | Site Map | Send Feedback
Reliable Controls® and the Reliable Controls® logo are registered trademarks of Reliable Controls Corporation. Copyright ©2010. All right reserved.