Supply Voltages
- 24 VAC/VDC ±15%
- 10 VA (SSC, SSCE)
- 58 VA (SSCP, including TRIAC output)
Display
- Four 0.6" digits, Six 0.3" characters
- Eleven icons: Auto, On, Off, Cool, Occupied, Heat, Fan, Fan Speed, AM, PM, and Day of the Week
- Backlit for easy viewing in dim light
- Display Area 36mm x 36mm (1.4" x 1.4")
Temperature Range
- 0 ºC to 40 ºC (32 ºF to 104 ºF)
Temperature Specifications
- 12-bit A/D converter
- Range: 0ºC to 40ºC (32ºF to 104ºF)
- ±0.1ºC (0.18ºF) resolution
- User calibrated to ±0.1ºC (0.18ºF) accuracy
Humidity Range (for H models)
- 0.1% resolution
- 10-90% range
- ±1.8% RH accuracy over range
|
|
Occupancy Sensor (for -OC models)
- Passive Infrared Radiation (PIR) sensor
- 64 detection zones
- 100º horizontal range
- 82º vertical range
- 5 m (16 ft.) detection distance
Buttons
- 3 custom silicon rubber buttons
- Button functions: select, plus, and minus
X-Port-2
- Access port for PC connection using X-Port-2 converter
Communications
- MS/TP BACnet slave @ 76800 baud max with AutoBaud
- Isolated EIA-485 transceiver, 2500 Vrms
- Up to 200 SSCs per network
- Requires 3 conductor network wire
Inputs
- 12-bit A/D convertor
- Dedicated temperature sensor
- Up to 3 universal inputs
- Jumper selectable 0-10 VDC, 4-20 mA, thermistor / dry contact
|
|
Outputs
- Up to 4 outputs (combination of universal and TRIAC)
- Universal supplies 12 VDC, 20 mA @ 12-bit DAC
- TRIAC switches 24VAC @ 0.5 A
Real-Time Clock (optional)
Memory/RTC Backup
- 72 hour backup
- 10 years for database
Dimensions
- 12 cm L x 7.0 cm W x 2.4 cm H (4.72" L x 2.75" W x 0.94" H)
Weight
Ambient Limits
- Operating: 0 ºC to 40 ºC (32 ºF to 104 ºF)
- Shipping: -40 ºC to 60 ºC (-40 ºF to 140 ºF)
- Humidity: 10% to 90% RH non-condensing
|
|