Carbon Dioxide (CO2) Monitoring - EQc1

Implementation CO2 Monitored by BAS
  • Installed carbon dioxide monitors throughout building
  • Integrated into the Building Automation System (BAS)
  • Sequenced the trickle vent dampers, wind tower dampers and AHU-1 to maintain CO2 setpoint
  • Programmed alarms if any CO2 levels exceed 1200 PPM
  • Despite the foregoing, this credit was denied because the system did not monitor the CO2 levels outside of the building