Small, durable and packed with flexibility, the Reliable Controls MACH-ProZone is a fully programmable BACnet Building Controller (B-BC) with highly scalable I/O in a very small footprint. The MACH-ProZone is ideal for a wide range of applications that include small to mid-sized roof top and heatpump applications, and small mechanical room applications.

Locate a Dealer

Features

Dynamic Database

  • Allows a maximum of 128 objects to be created of any supported type in any model of controller
  • Typical Object Configuration table (below) shows the usage of expanded memory


Protocol

  • BACnet® - MS/TP (EIA-485)


Control-BASIC Programs

  • 8500 bytes programmable control strategy in a readable, BASIC-like language
  • 3200 bytes per program


Inputs

  • Universal ranges
  • Soft-selectable 0-10 VDC,
    4-20 mA, thermistor / dry contact


Outputs

  • Universal ranges
  • Jumper selectable 0-12 VDC,
    or TRIAC


Variables

  • Selectable standard and custom ranges, as well as fixed or program-driven values

PID Loops

  • Standard P, PI, or PID controllers for closed loop control


Single-Point Trend Logs

  • Stores 128 samples at programmable time intervals


Multipoint Trend Logs

  • Each Trend Log stores 128 samples of 8 points at programmable time intervals


Runtime Report

  • Records the total On time and the total number of transitions, as well as daily transitions for every binary point
  • A 50 sample runtime log is optional for each binary point


System Groups

  • Allows related points to be grouped onto one display
  • 80 points/group


Schedules

  • 7 On/Off times for each weekday or exception


Calendars

  • Days of the year designated as holidays

Arrays

  • Up to 128 elements in a one-dimensional array


Tables

  • For creating custom input ranges and Control-BASIC lookup tables


Custom Units

  • 8 analog engineering units
  • 8 binary engineering units
  • 8 multistate units with 8 states, 32-characters each


SMART-Net Port

  • Networks up to 8
    SMART-Sensors


64 Network In Points


32 Network Out Points

  • The total maximum number of writes and shares to other devices


Warranty

  • 5 years


Certification

Typical Maximum Object Configuration

There are physical limitations to the number of inputs, outputs, and SMART-Sensors that can be connected to a MACH-ProZone controller. For other object types, there are no imposed limits for the maximum number of objects of a single type that can be created. The total number of objects (including inputs, outputs, and SMART-Sensors) is limited to 128, and is also limited by the onboard memory. The table below details typical databases that fit in all models.

Memory Variables Loops Schedules Calendars Tables* Groups Multipoint Trend** Runtime* Arrays Program SMART-Sensor***
-XM and
MPZ-88
64 8 4 2 4 4 10 128 4 8 8


* Tables and Runtime Logs are not counted in the 128 object limit. Inputs, outputs, and the device object are counted in the 128 object limit.
** Trends are configured to store 128 samples.
*** All models accommodate a maximum of 8 SMART-Sensors.

BTL Listed Device

Tech Specs

Processor & Memory

  • 66 MHz, high performance, 32-bit embedded microcontroller with onboard Flash memory
  • Controller database, values and configuration held in robust non-volatile memory
  • Operating System firmware easily updated at any time over the network


Supply Voltages

  • 24 VAC ±10% 25 VA max. 50/60 Hz
  • 24 VDC ±10% 12 W max.


Communications

  • EIA-485 @ 76.8 kbps max.
  • SMART-Net (8 SMART-Sensors max.)
  • Auto-baud detection


Universal Inputs

  • 12-bit A/D converter
  • Soft selectable: 0-10 VDC, 4-20 mA, thermistor/dry contact
  • Impedance:
    3M Ω on 0-10 VDC range
    250 Ω on 4-20 mA range
    20k Ω on thermistor range
  • Pulse counting up to 40 Hz
    (supports flow meters)
  • 24 VAC over-voltage protection


Universal Outputs

  • 12-bit D/A converter
  • Analog: 0-12 VDC
  • Binary: 0/12 VDC
  • Output power: 75 mA @ 12 VDC
  • 24 VAC over-voltage and short protection
  • Jumper selectable TRIAC


TRIAC Outputs

  • 24 VAC @ 0.5 A

SETUP-Tool

  • SETUP-Tool optional for configuration


Real-time Clock (optional

  • ±5 seconds per month


Memory/RTC Backup

  • 72 hour backup
  • 10 years for database


Terminal Blocks

  • 12 to 30 AWG (3.31 mm² to 0.05²)
  • Stranded or solid core
  • Copper conductors only


Dimensions

  • 10.9 cm L x 19.1 cm W x 4.9 cm H
  • (4 5/16" L x 7 1/2" W x 1 5/16" H)

Mounting

  • DIN rail, or
  • #8 clearance holes on 17.8 cm W (7" W) centerline


Weight

  • 0.3 kg (0.7 lb.)


Ambient Limits

  • Operating: -20 ºC to 55 ºC
    (-4 ºF to 131 ºF)
  • Shipping: -40 ºC to 60 ºC
    (-40 ºF to 140 ºF)
  • Humidity: 10% to 90%
    RH non-condensing

Application Diagram