EnOcean Transceiver
Wireless Transceiver

Aesthetically designed to suit any decor, the Reliable Controls EnOcean Transceiver opens the door for integration of a wide variety of EnOcean wireless sensors and control devices with the Reliable Controls system.

Purchase Products

Product features

EnOcean Enabled

  • EnOcean is the wireless standard for sustainable buildings.
  • Compatible with EnOcean Equipment Profiles (EEP) 4BS, 1BS, and RPS. For a full listing of compatible EEPs, refer to the last page of the EnOcean Transceiver submittal sheet.

Aesthetic Design

  • Slim profile with standard SS3 Thin Backplate.
  • Installs into standard electrical box.

868 MHz ASK Radio (-868 Model)

  • Uses amplitude-shift keying (ASK) radio.

902 MHz FSK Radio (-902 Model)

  • Uses frequency-shift keying (FSK) radio.

Programming

  • Use the MACH-ProLight EnOcean worksheet in the MACH‑ProLight controller.
  • Program up to 32 EnOcean devices.
  • EnOcean values are automatically stored as virtual BACnet value objects in the controller database. Some sensors support multiple transducers or values.

Connection

  • Easy four-wire terminal block connection.

Signal Strength Indication

  • Indicates received signal strength in software.

Warranty

  • 5 years.
RoHS 3 Certified

Technical specifications

Supply Voltage from Controller

  • 5 VDC at 35 mA.

Transceiver

  • Frequency: 868 MHz or 902 MHz.
  • Data rate: 125 kbps.
  • Receiver sensitivity at 25°C:
    • 868.3 MHz ASK: -93 dBm.
    • 902.875 MHz FSK: -98 dBm.
  • Conducted typical output power:
    • 868.3 MHz ASK: +10 dBm.
    • 902.875 MHz FSK: +1 dBm.

Transmission Range

  • 30 m (100 ft) line of sight maximum.

Connection

  • Recommended wire: 14-26 AWG (2.08–0.13 mm2), low capacitance <25 pF/ft), 30 m (100 ft) maximum distance.

EnOcean Port

  • EnOcean Serial Protocol.
  • 57.6 kbps EIA-232 serial data port.

Weight

  • 0.086 kg (0.19 lb).

Dimensions

  • 12 cm H x 7 cm W x 2.4 cm D
    (4 3/4” H x 2 3/4” W x 15/16” D).

Ambient Limits

  • Operating: 0°C to 50°C (32°F to 122°F).
  • Shipping: -25°C to 60°C (-13°F to 140°F).
  • Humidity: 10%–90% RH noncondensing.

Certifications

  • CE.
  • FCC CFR 47 Part 15 (TCM 515U).
  • R&TTE EN 300 220 (TCM 515).

Diagrams


SMART–Sensor EnOcean Accesspoint connection